( CHAPTER 16 STRUCTURAL LOADS ) <br /> (SECTION 1610.0 SNOW LOADS) <br /> <br />1610.3.1 Local Criteria. For purposes of this code, ground snow loads used <br />in determining the design snow loads for roofs shall be 20 psf. <br /> <br />(SECTION 1611.0 WIND LOADS) <br /> <br />1611.3.1 Local Criteria: For purposes of this code the basic wind speed shall be <br />seventy (70) miles per hour. <br /> <br />(SECTION 162.0 EARTHQUAKE LOADS) <br /> <br />1612.1.3.1 Local Criteria: For the purposes of this code Av (Figure 1612.1.3(1) <br />and Aa (Figure 1612.1.3(2)) shall both be equal to 0.13. <br /> <br />( CHAPTER 17 STRUCTURAL TESTS AND INSPECTIONS ) <br /> (SECTION 1705.0 SPECIAL INSPECTIONS) <br /> <br />1705.1 General: The permit applicant shall provide special inspections where application <br />is made for construction as described in this section. The special inspectors shall be <br />provided by the owner and shall be qualified and approved for the inspection of the work <br />described herein. <br /> <br />Exceptions <br /> 1. Special inspections are not required for work of a minor nature or where <br /> warranted by conditions in the jurisdiction. <br /> 2. Special inspections are not required for building components unless the design <br /> involves construction documents prepared by a registered design professional per <br /> Section 114.1. <br /> 3. Special inspections are not required for buildings of the R-3 Use Group that <br /> do not involve unusual soil conditions or unusual structural design. <br /> <br /> ( CHAPTER 18 FOUNDATIONS AND RETAINING WALLS ) <br /> (SECTION 1806.0 DEPTH OF FOOTINGS) <br /> <br /> 1806.1.1 Frost line: The frost line is established at 30 inches below finished <br /> grade. <br /> <br /> (SECTION 1813.0 WATERPROOFING AND DAMPPROOFING) <br /> <br />1813.3 Dampprooflng required: Where hydrostatic pressure will not occur as <br />determined by Section 1813.2, floors and walls for other than wood foundation systems <br />and unheated garages, shall be dampproofed in accordance with this section. Wood <br />foundation systems shall be constructed in accordance with NFoPA TR7 listed in Chapter <br />35. <br /> <br />-12- <br /> <br /> <br />